An explosion-proof electromagnetic flowmeter installed on a mixing station storage tank is critical for accurate liquid measurement and safe operation. When it faults, operators may see no signal, unstable readings, zero flow, alarm codes, or a mismatch between batch records and tank inventory. Common causes include empty or partially filled pipes, air pockets, incorrect grounding, loose or wet terminal connections, damaged electrodes, coating on the liner, low conductivity of the medium, power supply issues, and configuration errors. In hazardous areas, never open the housing or disconnect cables while the circuit is live. Isolate power, follow permit-to-work rules, and use suitable test instruments. First verify process conditions: confirm the tank has enough liquid, valves are open, and the pipe is full. Check the flowmeter display, power, fuse, and signal wiring. Inspect grounding and shielding, especially if readings fluctuate. Clean electrodes and liner only after safe isolation and according to the manufacturer's instructions. Compare the zero point and calibration settings. If the medium conductivity is too low, select a suitable meter or adjust installation. For explosion-proof models, ensure cable glands, seals, and enclosures remain intact. Record fault codes and maintenance actions. Preventive measures include regular zero checks, terminal inspections, grounding tests, liner cleaning, calibration verification, and operator training. Prompt diagnosis reduces downtime and protects the mixing station.